• Genuine OEM refrigerant pressure switch for Heatcraft refrigeration equipment, including unit coolers and condensing units
• This switch monitors refrigerant pressure and opens or closes a control circuit at a set point, either as a safety that stops the compressor or as a control that cycles a condenser fan
• Heatcraft factory part # 28903201 - confirm the part number against your unit before ordering

Details
Pressure switches fail from contact wear, a fatigued diaphragm, or leaks at the fitting. A bad switch can lock the compressor out with normal pressures, or fail to open during a real fault. Always confirm actual system pressure with gauges first, since a tripping switch usually points to a dirty coil, failed fan, airflow problem, or incorrect charge.
Replacement should be performed by an EPA-certified HVAC technician. Lock out power and disconnect the leads. If the switch threads onto a Schrader-type access fitting it can be changed without recovering the charge; otherwise recover refrigerant first. Install the new switch with the same set points, leak-check the fitting, and verify operation.
Product Specs
Dimensions |
LENGTH4 in HEIGHT1 in WEIGHT0.005 lbs |
-
Decades of Expertise
The parts you trust from a team who knows them best. We’re here for you, we have the know-how, and your success matters to us.
-
Fast Same Day Shipping
From a company that understands parts delivery on demand: sleep tight, we’re on it.
-
Hassle Free Returns
Returns are a fact of online life. Contact our team and we’ll take care of it.
- Choosing a selection results in a full page refresh.
- Opens in a new window.